Parameters
All room setpoint temperatures for the operating modes activated are displayed on the web user interface.
Change the related room setpoint temperatures using the
users with the exception of the "Viewer" have the right to change these values.
The room setpoint temperatures can be set in the range from 0 °C – 50 °C. A validation process makes
sure only the following sequence can be set:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Every room setpoint temperature must equal to or greater than the previous. Furthermore, the dead band
set must be respected.
Cooling Building Protection
Cooling Economy
Cooling Standby
Cooling Comfort
Dead band
Heating Comfort
Heating Standby
Heating Economy
Heating Building Protection
and
buttons or using the keyboard. All