ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 264

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Output sockets
Object name
Valve control value
The module has this output socket if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
type
Outputs the valve control value for the heating distribution circuit. This value is received from the heating distribution circuit
controller linked via the related module group object
Signal value:
Supply temperature
Outputs the current supply temperature that is received via the related group object.
Signal value:
Return temperature
Outputs the current return temperature that is received via the related group object.
Signal value:
Control On/Off
The module has this output socket in the following conditions:
If the Yes option is selected for the
heating distribution circuit control based on ASM input socket
If the Yes option is selected for the
Outputs the status of the control that is sent to the heating distribution circuit controller via the related group object. The state
is dependent on the Enable heating distribution circuit control based on ASM input socket and Switch off if no room demand
parameters.
Signal value:
264 2CDC508198D0211 Rev. A | AC/S 1.x.1
parameter.
0...100%
-273...670760 °C
-273...670760 °C
0 = Off
1 = On
Supply temperature control
parameter and the Yes option is selected for the
parameter.
Switch off if no room demand
parameter.
Data type
DPT 5.001
Valve
DPT 9.001
DPT 9.001
DPT 1.001
Enable