Parameters
BACnet/IP Foreign Device
Options:
Use this parameter to activate the function with which the device registers as BACnet/IP foreign device on
a remote BACnet Broadcast Management Device (BBMD). This is necessary if the device is in a different
IP subnet to the rest of the BACnet devices.
Selection of Yes option:
No (checkbox cleared)
Yes (checkbox selected)
Dependent parameter(s):
Foreign Device Address
Information on the IP address and the port used by the BACnet Broadcast Management Device
(BBMD). This setting must match the setting on the BBMD.
The information must always consist of the IP address followed by the port number. IP address and
port number must be separated by a colon, e.g. 192.168.1.10:47808
Foreign Device Registration Time
Options:
1...60...65535 s
Information on the interval in seconds at which the device renews its registration on the BACnet
Broadcast Management Device (BBMD). This setting must match the setting on the BBMD.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 61