Object function
In-/Output: Valve override disable/enable
The module has this group object if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
type
This object activates/deactivates the valve (mixing valve) override for the heating distribution circuit controller.
Telegram value:
In-/Output: Valve override control value
The module has this group object if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
type
This object specifies the control value (valve position) used to override the valve for the heating distribution circuit if the valve
override is active.
Telegram value:
Input: Status Valve purge
The module has this group object if the 3-way valve (mixing valve) option or the 2-way valve option is selected for the
type
Input for the status of the heating distribution circuit controller as to whether a valve purge is currently in progress.
Telegram value:
Input: Pump A repair switch status
The module has this group object if the Yes option is selected for the
The status of the repair switch for the pump can be received via this group object and evaluated by the device.
Telegram value:
272 2CDC508198D0211 Rev. A | AC/S 1.x.1
parameter and the Yes option is selected for the
0 = Disabled
1 = Enabled
parameter and the Yes option is selected for the
0...100 %
parameter and the Yes option is selected for the
0 = Inactive
1 = Active
0 = Inactive
1 = Active
Name (can be changed separately)
Heating distribution circuit
Valve override disable/enable
Heating distribution circuit
Valve override disable/enable
Heating distribution circuit
Status Valve purge
parameter.
Heating distribution circuit
Display pump repair switch status
Data type
Flags
1 bit
C, R, W, T
DPT 1.003
parameter.
1 byte
C, R, W, T
DPT 5.001
parameter.
1 bit
C, W, T
DPT 1.011
1 bit
C, W, T
DPT 1.011
parameter.
Valve
Valve
Valve