KNX
Parameters
Use value after restart
Options:
This parameter specifies which value is output in the group object and on the web user interface after
starting the application controller until a new value is received on the ASM input socket.
Last value: The last value before device start is saved and reused. The value parameterized further
down in Initial value is used after the first download of the module to the application controller.
Initial value: The value described further down in Initial value is used.
Send value to KNX by a change of
Options:
This parameter changes the send behavior. The value is only sent on the KNX bus if the new value differs
from the last value sent by the difference set. The value "0" means that this function is not active and any
value change is sent on the bus. This function affects only the output on the KNX bus. The last value is
always output on the ASM output socket.
Send cyclically values to KNX
Options:
This parameter specifies whether the value is to be sent cyclically on the KNX bus.
No (checkbox cleared): The value is only sent on the KNX bus after a change.
Yes (checkbox selected): The value is sent on the KNX bus after every change and cyclically. The
cycle time is set in the Send cyclically values to KNX every parameter below and is restarted each
time on sending after a change.
Selection of Yes option:
Last value
Initial value
0...1...670760 °C
(Value range dependent on the data point type selected)
No (checkbox cleared)
Yes (checkbox selected)
Dependent parameter(s)
Send cyclically values to KNX every
Options:
00:10:00...01:00:00...23:59:00 [hh:mm:ss]