ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 377

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Supply setpoint temperature
In this parameter window it is specified how the supply setpoint temperature for the chiller is calculated.
Supply temperature control
Options:
On the selection of the Yes option, the ASM calculates the supply setpoint temperature for the chiller and
sends the value calculated to the chiller via the group object. Other parameters define how the calculation
is undertaken.
Selection of Yes option:
Dependent parameter(s):
No (checkbox cleared)
Yes (checkbox selected)
Supply setpoint temperature source
Options:
ASM input socket
WebUI Input
BACnet input object
Calculated weather compensated
This parameter determines how the supply setpoint temperature is determined for the chiller. This
setpoint is sent to the chiller via the group object.
ASM input socket: The supply setpoint temperature received via the input socket on the ASM is
used. This is an ASM multiple socket on which the lowest value present is used.
WebUI Input: The supply setpoint temperature is set on the web user interface for the ASM.
BACnet input object: The supply setpoint temperature received via the BACnet object for the
ASM is used.
Calculated weather compensated: The module calculates the supply setpoint temperature
currently required based on the outside temperature.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 377

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac/s 1.2.1Ac/s 1.1.1

Table of Contents