ABB i-bus
KNX
Parameters
Object name
Cooling distribution circuit: Pump A operating status (Off/On)
The module has this BACnet output object if the Yes option is selected for the
Outputs the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the cooling distribution circuit controller.
Signal value:
Cooling distribution circuit: Pump A relay status
Outputs the status of the cooling distribution circuit controller's pump.
Signal value:
Cooling distribution circuit: Pump A fault
The module has this BACnet output object if the Yes option is selected for the
Outputs the fault status provided by the pump.
Signal value:
Cooling distribution circuit: Pump A repair switch status
The module has this BACnet output object if the Yes option is selected for the
Outputs the contact position provided by the pump repair switch.
Signal value:
Cooling distribution circuit: Pump B override disable/enable
The module has this BACnet output object if the Yes option is selected for the
selected for the
Outputs whether the second pump for the cooling distribution circuit is overridden.
Signal value:
0 = Inactive
1 = Active
0 = Off
1 = On
0 = Inactive
1 = Active
0 = Inactive
1 = Active
Override by WebUI
parameter.
0 = Disabled
1 = Enabled
Object type
Unit
Binary value
-
Pump display operating status
parameter.
Binary value
-
Binary value
-
Pump display pump fault status
Binary value
-
Display pump repair switch status
Binary value
-
Double pump
parameter and the Yes option is
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 365
COV send
condition
-
-
-
parameter.
-
parameter.
-