Bacnet Parameter Page - ABB i-bus KNX AC/S 1.x.1 Series Product Manual

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.2.2.3

BACnet parameter page

This parameter page is only available on the AC/S 1.2.1 Application Controller BACnet.
BACnet server enable
Options:
Use this parameter to enable/disable the device's BACnet function globally. If the BACnet server is
disabled, it is not possible to communicate with the device via BACnet.
BACnet device object instance number
Options:
Definition of the BACnet device address.
The BACnet device address must be unique in the BACnet network and is not allowed to be assigned
twice.
BACnet device object name
Definition of the BACnet name of the device. The device uses this name in the BACnet network.
BACnet protocol port
Options:
Definition of the IP port the BACnet server uses. This port must be set to suit the BACnet network.
60 2CDC508198D0211 Rev. A | AC/S 1.x.1
No (checkbox cleared)
Yes (checkbox selected)
0...194302
Note
47808...47823, 49152...65535