Bacnet Objects - ABB i-bus KNX AC/S 1.x.1 Series Product Manual

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.9.5

BACnet objects

Type
Input
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
276 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Heating distribution circuit: Supply setpoint temperature External
specification
Heating distribution circuit: Return temperature
Heating distribution circuit: Supply temperature
Heating distribution circuit: Supply setpoint temperature status
Heating distribution circuit: Outside temperature
Heating distribution circuit: Supply setpoint temperature override
status
Heating distribution circuit: Supply setpoint temperature External
specification
Heating distribution circuit: Operation mode
Heating distribution circuit: Room setpoint temperature Comfort
Heating distribution circuit: Room setpoint temperature Standby
Heating distribution circuit: Room setpoint temperature Economy
Heating distribution circuit: Room setpoint temperature Building
Protection
Heating distribution circuit: Max. room setpoint temperature
Heating distribution circuit: Control On/Off
Heating distribution circuit: Room involvement
Heating distribution circuit: Control On/Off override disable/enable
Heating distribution circuit: Room control values
Heating distribution circuit: Pump A override disable/enable
Heating distribution circuit: Pump A override value
Heating distribution circuit: Pump A operating status (Off/On)
Heating distribution circuit: Pump A relay status
Heating distribution circuit: Pump A fault
Heating distribution circuit: Pump A repair switch status
Heating distribution circuit: Pump B override disable/enable
Heating distribution circuit: Pump B override value
Heating distribution circuit: Pump B operating status (Off/On)
Heating distribution circuit: Pump B relay status
Heating distribution circuit: Pump B fault
Heating distribution circuit: Pump B repair switch status
Heating distribution circuit: Valve control value
Heating distribution circuit: Valve override disable/enable
Heating distribution circuit: Valve override control value
Heating distribution circuit: Status Valve purge
Object type
Unit
COV send
condition
Analog value
°C (62)
-
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Binary value
-
Analog value
°C (62)
1.0
Positive integer
No unit
1.0
value
(95)
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Analog value
°C (62)
1.0
Binary value
-
-
Analog value
°C (62)
1.0
Binary value
-
-
Analog value
% (98)
1.0
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Binary value
-
Analog value
% (98)
1.0
Binary value
-
Analog value
% (98)
1.0
Binary value
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-