ABB i-bus
KNX
Parameters
Switch off if no room demand
Options:
With this function the module monitors the room control values and automatically switches on and off the
chiller connected accordingly.
It is a prerequisite for this function that all control values from the room valves in the cooling system are
available and connected to the ASM input socket. There must therefore not be any conventional
thermostats in the cooling system.
This function is affected by the
activated, the Enable chiller based on ASM input socket has a higher priority.
Selection of Yes option:
380 2CDC508198D0211 Rev. A | AC/S 1.x.1
Min. supply temperature
Options:
0...3...100 °C
The supply setpoint temperature output by the module is limited using this parameter. This is a
safety function that ensures a supply setpoint temperature too low for the cooling system is not
output under any circumstances. For example, the supply setpoint temperature for cooling ceiling
can be limited to minimum 14 °C.
No (checkbox cleared)
Yes (checkbox selected)
Enable chiller based on ASM input socket
Dependent parameter(s)
Switch on if the room demand is higher than
Options:
0...10...100 %
The module sends a switch-on command to the chiller if the highest room control value present on
the ASM input socket exceeds this value.
Switch off if the room demand is equal to or less than
Options:
0...100 %
The module sends a switch-off command to the chiller if the highest room control value present on
the ASM input socket is the same as or less than this value.
function. If both functions are