Parameters
Object name
Pump B override disable/enable
The module has this output socket if the Yes option is selected for the
for the
Outputs whether the second pump for the cooling distribution circuit is overridden.
Signal value:
Pump B override value
The module has this output socket if the Yes option is selected for the
for the
Outputs the state with which the second pump for the cooling distribution circuit is overridden if the pump override is active.
Signal value:
Supply setpoint temperature
The module has this output socket if the Yes option is selected for the
Outputs the current supply setpoint temperature as is sent by the module to the cooling distribution circuit controller via the
related group object. The supply setpoint temperature output here is, depending on the setting, either calculated by this
module based on the outside temperature, or specified via an ASM input socket or BACnet and also takes into account any
possible override of the supply setpoint temperature via the web user interface.
Signal value:
Supply setpoint temperature External specification
This module has this output socket if the Yes option is selected for the
input object option is selected for the
Outputs the supply setpoint temperature specified via the BACnet object. This status does not take into account any possible
override of the supply setpoint temperature via the web user interface.
Signal value:
354 2CDC508198D0211 Rev. A | AC/S 1.x.1
Override by WebUI
parameter.
0 = Disabled
1 = Enabled
Override by WebUI
parameter.
0 = Off
1 = On
-273...670760 °C
Supply setpoint temperature source
-273...670760 °C
Data type
DPT 1.003
Double pump
parameter and the Yes option is selected
DPT 1.001
Double pump
parameter and the Yes option is selected
DPT 9.001
Supply temperature control
parameter.
DPT 9.001
Supply temperature control
parameter and the BACnet
parameter.