Group Objects - ABB i-bus KNX AC/S 1.x.1 Series Product Manual

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.10.4

Group objects

Object function
Input: Supply temperature
Input: Return temperature
Output: Supply setpoint temperature
Input: Pump relay status
Output: Heat generator On/Off
Input: Heat generator operating status
Input: Heat generator failure status
In-/Output: Pump override disable/enable
In-/Output: Pump override value
Input: Pump operating status (Off/On)
Input: Pump fault
Input: Pump repair switch status
318 2CDC508198D0211 Rev. A | AC/S 1.x.1
Name (can be
Data point type
changed
(DPT)
separately)
Heat generator
9.001
Heat generator
9.001
Heat generator
9.001
Heat generator
1.001
Heat generator
1.001
Heat generator
1.011
Heat generator
1.011
Heat generator
1.003
Heat generator
1.001
Heat generator
1.011
Heat generator
1.011
Heat generator
1.011
Length
Flags
C R W T
U I
2 bytes
x
x
x
2 bytes
x
x
x
2 bytes
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x
x
1 bit
x
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x

Advertisement