ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 393

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
BACnet output objects
Object name
Chiller: Return temperature
Outputs the current return temperature that is received via the related group object.
Signal value:
Chiller: Supply temperature
Outputs the current supply temperature that is received via the related group object.
Signal value:
Chiller: Supply setpoint temperature status
The module has this BACnet output object if the Yes option is selected for the
Outputs the current supply setpoint temperature as is sent by this module to the chiller via the related group object. The supply
setpoint temperature output here is, depending on the settings, either calculated by this module based on the outside
temperature, or specified via an ASM input socket or BACnet and also takes into account any possible override of the supply
setpoint temperature via the web user interface.
Signal value:
Chiller: Outside temperature
This module has this BACnet output object if the Yes option is selected for the
Calculated weather compensated option is selected for the
Outputs the current outside temperature that is used by the module for the calculation.
Signal value:
Chiller: Supply setpoint temperature override status
This module has this BACnet output object if the Yes option is selected for the
ASM input socket option, BACnet input object option or the Calculated weather compensated option is selected for the
setpoint temperature source
Outputs whether the supply setpoint temperature has been overridden via the web user interface.
Signal value:
-273...670760 °C
-273...670760 °C
-273...670760 °C
-273...670760 °C
parameter.
0 = Not overridden
1 = Overridden
Object type
Analog value
Analog value
Analog value
Supply temperature control
Analog value
Supply temperature control
Supply setpoint temperature source
Binary value
Supply temperature control
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 393
Unit
COV send
condition
°C (62)
1.0
°C (62)
1.0
°C (62)
1.0
parameter.
°C (62)
1.0
parameter and the
parameter.
-
-
parameter and the
Supply

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac/s 1.2.1Ac/s 1.1.1

Table of Contents