Object name
Heating distribution circuit: Room setpoint temperature Comfort
This module has this BACnet output object if the Yes option is selected for the
Calculated weather compensated option is selected for the
Scheduler option is selected for the
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Comfort operating mode if this operating mode is active.
Signal value:
Heating distribution circuit: Room setpoint temperature Standby
This module has this BACnet output object if the Yes option is selected for the
Calculated weather compensated option is selected for the
Scheduler option is selected for the
mode Standby parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Standby operating mode if this operating mode is active.
Signal value:
Heating distribution circuit: Room setpoint temperature Economy
This module has this BACnet output object if the Yes option is selected for the
Calculated weather compensated option is selected for the
Scheduler option is selected for the
mode Economy parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Economy operating mode if this operating mode is active.
Signal value:
Heating distribution circuit: Room setpoint temperature Building
Protection
This module has this BACnet output object if the Yes option is selected for the
Calculated weather compensated option is selected for the
Scheduler option is selected for the
operating mode Building Protection parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Building Protection operating mode if this operating mode is active.
Signal value:
Economy mode
parameter.
-273...670760 °C
Economy mode
parameter and the Yes option is selected for the Scheduler operating
-273...670760 °C
Economy mode
parameter and the Yes option is selected for the Scheduler operating
-273...670760 °C
Building Protection mode
-273...670760 °C
Object type
Analog value
Supply temperature control
Supply setpoint temperature source
Analog value
Supply temperature control
Supply setpoint temperature source
Analog value
Supply temperature control
Supply setpoint temperature source
Analog value
Supply temperature control
Supply setpoint temperature source
parameter and the Yes option is selected for the Scheduler
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 279
Unit
COV send
condition
°C (62)
1.0
parameter, the
parameter and the Based on
°C (62)
1.0
parameter, the
parameter, the Based on
°C (62)
1.0
parameter, the
parameter, the Based on
°C (62)
1.0
parameter, the
parameter, the Based on