ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 372

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Supply temperature page
On this page it is shown how the supply setpoint temperature is calculated. The settings on which the
calculation is based can be changed.
The information displayed on this page may vary depending on which settings have been selected for the
supply setpoint temperature calculation in the ASM settings.
This section displays the current outside temperature that is used by the module for the calculation.
The parameter set in the ASM settings can be changed in this section via the web user interface. This is
advantageous so that the settings can be adapted to the local situation during the operating of the system
without renewed ETS programming.
The settings on the web user interface always apply. The parameters set in the ASM settings are
overwritten and only become active again on the reinstallation of the ASM.
The supply setpoint temperature output by the module is limited using the Min. supply temperature
parameter. This is a safety function that ensures a supply setpoint temperature too low for the cooling
system is not output under any circumstances. For example, the supply setpoint temperature for cooling
ceiling can be limited to minimum 14 °C.
372 2CDC508198D0211 Rev. A | AC/S 1.x.1