ABB i-bus
KNX
Parameters
Radiator
Options:
Selects the radiator.
•
None: A radiator is not used in the room
•
On/Off: The radiator has a valve with the two settings open/closed, e.g. a solenoid valve. KNX DPT
1.001 is used.
•
0...100%: The radiator has a continuous valve, e.g. a thermal or motorized valve. KNX DPT 5.001 is
used.
Floor heating
Options:
Selects the floor heating.
•
None: Floor heating is not used in the room.
•
On/Off: The floor heating has a valve with the two settings open/closed, e.g. a solenoid valve. KNX
DPT 1.001 is used.
•
0...100%: The floor heating has a continuous valve, e.g. a thermal or motorized valve. KNX DPT
5.001 is used.
Selection of On/Off and 0...100% option:
None
On/Off
0...100%
None
On/Off
0...100%
Dependent parameter(s):
Floor temperature sensor
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether the value measured by the floor temperature sensor is displayed
on the web user interface and is to be output in the BACnet object and on the ASM output socket.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 193