ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 157

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
BACnet to KNX with update
A value received via the BACnet object is sent by the group object using this template. A value received
from the KNX bus is transmitted back to the BACnet object. The value is also output on the web user
interface and on the ASM output socket for linking to other modules.
The settings for the ASM socket, web user interface, KNX and BACnet are set automatically as follows:
ASM socket:
WebUI:
KNX:
BACnet:
Main data point type
Data point type
Definition of the data point type that is transferred between the interfaces.
You will find further information on the data point types in
Use value after restart
Options:
This parameter defines which value is output in the group object and on the ASM output socket after
starting the application controller until a new value is received in the group object.
Last value: The last value before device start is saved and reused. The value parameterized further
down in Initial value is used after the first download of the module to the application controller.
Initial value: The value described further down in Initial value is used.
Output
Display
Input + output
Read + writable by BACnet
Last value
Initial value
chapter 4.7 Data point
types.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 157