ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 112

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Function
If the current time is between the start time and end time AND the Active input = 1 (true):
o
Start time greater than end time:
o
Active input = 0 (false):
o
Active input = 1 (true):
o
Whole time input = 1 (true) AND Active input = 1 (true):
o
o
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
Exception handling and startup behavior
The element does not work if:
The system time is invalid.
Start time or end time have invalid or no values.
The function element only works with start and end time. The weekdays contained in the DPT are
ignored.
112 2CDC508198D0211 Rev. A | AC/S 1.x.1
Output = 1 (true)
Output = 0 (false)
The output remains unchanged.
The output is recalculated and updated accordingly.
Output = 1 (true)
The element reacts as if the start time and end time were both 00:00.