ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 262

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Room setpoint temperature Comfort
This module has this input socket if the Yes option is selected for the
weather compensated option is selected for the
option is selected for the
Input for the room setpoint temperature in the Comfort operating mode for the heating operating type for the rooms connected
to the heating distribution circuit. The module selects the highest value and uses this value for the Economy mode function to
adjust the heating curve and therefore the supply setpoint temperature to the current needs.
Signal value:
Room setpoint temperature Standby
This module has this input socket if the Yes option is selected for the
weather compensated option is selected for the
option is selected for the
parameter.
Input for the room setpoint temperature in the Standby operating mode for the heating operating type for the rooms connected
to the heating distribution circuit. The module selects the highest value and uses this value for the Economy mode function to
adjust the heating curve and therefore the supply setpoint temperature to the current needs.
Signal value:
Room setpoint temperature Economy
This module has this input socket if the Yes option is selected for the
weather compensated option is selected for the
option is selected for the
Economy parameter.
Input for the room setpoint temperature in the Economy operating mode for the heating operating type for the rooms
connected to the heating distribution circuit. The module selects the highest value and uses this value for the Economy mode
function to adjust the heating curve and therefore the supply setpoint temperature to the current needs.
Signal value:
Room setpoint temperature Building Protection
This module has this input socket if the Yes option is selected for the
weather compensated option is selected for the
option is selected for the
Protection parameter.
Input for the room setpoint temperature in the Building Protection operating mode for the heating operating type for the rooms
connected to the heating distribution circuit. The module selects the highest value and uses this value for the Economy mode
function to adjust the heating curve and therefore the supply setpoint temperature to the current needs.
Signal value:
262 2CDC508198D0211 Rev. A | AC/S 1.x.1
Supply setpoint temperature source
Economy mode
parameter.
-273...670760 °C
Supply setpoint temperature source
Economy mode
parameter and the Yes option is selected for the Scheduler operating mode Standby
-273...670760 °C
Supply setpoint temperature source
Economy mode
parameter and the Yes option is selected for the Scheduler operating mode
-273...670760 °C
Supply setpoint temperature source
Economy mode
parameter and the Yes option is selected for the Scheduler operating mode Building
-273...670760 °C
Data type
DPT 9.001
Supply temperature control
parameter, the Calculated
parameter and the Based on Scheduler
DPT 9.001
Supply temperature control
parameter, the Calculated
parameter, the Based on Scheduler
DPT 9.001
Supply temperature control
parameter, the Calculated
parameter, the Based on Scheduler
DPT 9.001
Supply temperature control
parameter, the Calculated
parameter, the Based on Scheduler