ABB i-bus
KNX
Parameters
7.12.4
Group objects
Object function
Input: Supply temperature
Input: Return temperature
Output: Supply setpoint temperature
Input: Pump relay status
Input: Pump repair switch status
Input: Pump fault
Input: Pump operating status (Off/On)
In-/Output: Pump override disable/enable
In-/Output: Pump override value
Output: Chiller On/Off
Input: Chiller operating status
Input: Chiller fault status
388 2CDC508198D0211 Rev. A | AC/S 1.x.1
Name (can be
Data point type
changed
(DPT)
separately)
Chiller
9.001
Chiller
9.001
Chiller
9.001
Chiller
1.001
Chiller
1.011
Chiller
1.011
Chiller
1.011
Chiller
1.003
Chiller
1.001
Chiller
1.001
Chiller
1.011
Chiller
1.011
Length
Flags
C R W T
U I
2 bytes
x
x
x
2 bytes
x
x
x
2 bytes
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x
x
1 bit
x
x
x
x
1 bit
x
x
x
1 bit
x
x
x
1 bit
x
x
x