Sockets - ABB i-bus KNX AC/S 1.x.1 Series Product Manual

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
7.13.3

Sockets

Overview of the ASM sockets for linking to other modules:
Type
Input
Output
Output
Output
Input sockets
Object name
Temperature
Either the outside temperature or the supply temperature must be connected to this input socket, depending on the setting
selected above. The changeover between heating and cooling is undertaken based on the temperature present here.
Signal value:
Output sockets
Object name
Operating type
Outputs the active operating type
Signal value:
Heating
Outputs the state of the heating operating type.
Signal value:
Cooling
Outputs the state of the cooling operating type.
Signal value:
406 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Temperature
Operating type
Heating
Cooling
-273...670760 °C
0 = Cooling
1 = Heating
0 = Off
1 = On
0 = Off
1 = On
Data type
9.001
1.100
1.001
1.001
Data type
DPT 9.001
Data type
DPT 1.100
DPT 1.001
DPT 1.001

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac/s 1.2.1Ac/s 1.1.1

Table of Contents