ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 209

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object function
Output: Operating mode normal (slave)
The module has this group object if the Display+set (slave) option is selected for the
This group object is used for synchronization of the operating mode between the Room ASM (slave) and the room thermostat
(master). For this purpose the group object must be connected to the controller's (master's) group object of the same name.
The Room ASM sends the operating mode to the controller in this group object.
Telegram value:
Input: Operating mode override (slave)
The module has this group object if the Display+set (slave) option is selected for the
This group object is used for synchronization of the overridden operating mode between the Room ASM (slave) and the room
thermostat (master). For this purpose the group object must be connected to the controller's (master's) group object of the
same name.
The Room ASM receives the current overridden operating mode from the controller in this group object.
Telegram value:
Input: Window status
The module has this group object if the Yes option is selected for the
Input for the connection of the window status.
Telegram value:
Name (can be changed
separately)
Room
0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
Room
0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
Room
0 = Closed
1 = Open
Data type
1 byte
DPT 20.102
Operating mode
1 byte
DPT 20.102
Operating mode
1 bit
DPT 1.019
Window status
parameter.
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 209
Flags
C, T
parameter.
C, W, T, U
parameter.
C, W, T, U