ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 196

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Output sockets
Object name
Actual room temperature
Outputs the actual room temperature
Signal value:
Room setpoint temperature
Outputs the current room setpoint temperature.
Signal value:
Controller On/Off
The module has this output socket if any option except None is selected for the
Outputs whether the room thermostat is switched on or off.
Signal value:
Heating/cooling operating type
The module has this output socket if any option except None is selected for the
Outputs the current heating/cooling operating type.
Signal value:
Operating mode
The module has this output socket if any option except None is selected for the
Outputs the current HVAC operating mode.
Signal value:
196 2CDC508198D0211 Rev. A | AC/S 1.x.1
-273...670760 °C
-273...670760 °C
0 = Off
1 = On
0 = Cooling
1 = Heating
0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
Data type
DPT 9.001
DPT 9.001
DPT 1.001
Controller On/Off
parameter.
DPT 1.100
Heating/cooling operating type
DPT 20.102
Operating mode
parameter.
parameter.