ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 194

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Cooling ceiling
Options:
Selects the cooling ceiling.
None: A cooling ceiling is not used.
On/Off: The cooling ceiling has a valve with the two settings open/closed, e.g. a solenoid valve. KNX
DPT 1.001 is used.
0...100%: The cooling ceiling has a continuous valve, e.g. a thermal or motorized valve. KNX DPT
5.001 is used.
Selection of On/Off and 0...100% option:
Split unit
Options:
This parameter specifies whether the status of a split unit (the usual terms are for example: split unit, air
conditioner, AC) in the room is displayed on the web user interface and is to be output in the BACnet
object and on the ASM output socket.
194 2CDC508198D0211 Rev. A | AC/S 1.x.1
None
On/Off
0...100%
Dependent parameter(s):
Cooling ceiling, dew point alarm sensor
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether the status of the dew point alarm sensor is displayed on the web
user interface and is to be output in the BACnet object and on the ASM output socket.
No (checkbox cleared)
Yes (checkbox selected)