ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 212

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object function
Input: Fan coil unit, fan speed confirm (slave)
This group object is used for synchronization of the fan speed status between the Room ASM (slave) and the room thermostat
(master). For this purpose the group object must be connected to the controller's (master's) group object of the same name.
In this group object the room thermostat (master) confirms the change in the fan speed to the Room ASM (slave).
The data point type for the group object is dependent on the settings in the module:
If any option except None is selected for the
selected for the
DPT 5.001
Telegram value 0...100 %
The fan speed in percent is transmitted, e.g. 50 %. Fan speeds are converted into the corresponding percentage.
If any option except None is selected for the
selected for the
DPT 5.010
Telegram value 0 ... 5
The fan speed is transmitted
Input: Fan coil unit, fan manual confirm (slave)
The module has this group object if any option except None is selected for the
(slave) DPT 5.001 option or Display+Set (Slave) DPT 5.010 option is selected for the
This group object is used for synchronization of the fan speed status between the Room ASM (slave) and the room thermostat
(master). For this purpose the group object must be connected to the controller's (master's) group object of the same name.
In this group object the room thermostat (master) confirms to the Room ASM (slave) whether the current fan speed has been
adjusted manually by a user or it was calculated automatically by the room thermostat.
Telegram value:
212 2CDC508198D0211 Rev. A | AC/S 1.x.1
Fan coil unit
Fan coil unit, fan speed
parameter:
Fan coil unit
Fan coil unit, fan speed
parameter:
0 = Automatic
1 = Manual
Name (can be changed
separately)
Room
parameter and the Display+set (slave) DPT 5.001 option is
parameter and the Display+set (slave) DPT 5.010 option is
Room
Fan coil unit
Data type
Flags
1 byte DPT 5.001
C, W, T, U
1 byte DPT 5.010
1 bit
C, W, T, U
DPT 1.011
parameter and the Display+set
Fan coil unit, fan speed
parameter.