Parameters
KNX to WebUI
The value received in the group object is displayed on the web user interface using this template. This
value is also output on the ASM output socket for linking to other modules.
The settings for the ASM socket, web user interface, KNX and BACnet are set automatically as follows:
ASM socket:
WebUI:
KNX:
BACnet:
Main data point type
Data point type
Definition of the data point type that is transferred between the interfaces.
You will find further information on the data point types in
Use value after restart
Options:
This parameter defines which value is output on the web user interface and the ASM socket after starting
the application controller until a new value is received in the group object.
Last value: The last value before device start is saved and reused. The value parameterized further
down in Initial value is used after the first download of the module to the application controller.
Initial value: The value described further down in Initial value is used.
144 2CDC508198D0211 Rev. A | AC/S 1.x.1
Output
Display
Input from KNX
None
Last value
Initial value
chapter 4.7 Data point