ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 185

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Interfaces
In the following parameters, activate the functions available in the KNX HVAC room automation devices. In
this way the related group objects for linking to the KNX HVAC room automation objects are shown in the
module. Furthermore, the web user interface for the module is generated and the ASM output sockets and
BACnet objects are activated based on these settings.
Room setpoint temperature
Options:
This parameter specifies whether the room setpoint temperature from the room thermostat received via
KNX is only to be displayed on the web user interface, or it can also be changed by the user. The current
value is output on the ASM output socket and in a BACnet object.
Display: The room setpoint temperature is only displayed on the web user interface and cannot be
changed.
Display+set (slave) DPT 9.001/DPT 9.002: The room setpoint temperature can be changed on the
web user interface.
This setting functions only with ABB and Busch-Jaeger devices with the new master/slave interface
with group objects of type DPT 9.001 (absolute temperature) / DPT 9.002 (relative temperature).
Display+set (slave) DPT 6.010: The room setpoint temperature can be changed on the web user
interface.
This setting functions only with ABB and Busch-Jaeger devices with the old master/slave interface
with a group object of type DPT 6.010 (counter pulses).
Display
Display+set (slave) DPT 9.001/DPT 9.002
Display+set (slave) DPT 6.010
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 185