ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 113

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Calendar (CALENDAR)
Used for events that occur periodically or on specific dates. A wide variety of settings is possible.
The calendar uses the logic device's internal clock. It can be changed via the bus (group objects).
The output value is 1 if the device time is between Start and End and the other conditions are met.
Inputs
No.
1
2
3
4
5-7
8
9
DPT
Abbr.
Name
Time
S
Start
Time
E
End
1 bit
A
Active
Whole
1 bit
WT
time
Date
A
Start
Date
B
End
Visible
Description
Defines the start time;
Parametrizable
refers to corresponding parameters
Defines the end time;
Parametrizable
refers to corresponding parameters
If Active = 0 the output is always 0;
Parametrizable
refers to corresponding parameters
If Whole time = 1, Start = 00:00:00 and
Parametrizable
End = 24:00:00;
refers to corresponding parameters
Recurrence (Daily, Weekly, Monthly, Yearly);
see below
Defines the date for activation of the calendar
element (sets a duration);
Parametrizable
before this date, the output value is 0;
refers to corresponding parameters
Defines the date for deactivation of the
calendar element (sets a duration);
Parametrizable
after this date, the output value is 0;
refers to corresponding parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 113