ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 353

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Object name
Pump B operating status (Off/On)
The module has this output socket if the Yes option is selected for the
for the
Outputs the operating status (Off/On) provided by the second pump. On pumps with their own control, this operating status
can differ from the operating status of the cooling distribution circuit controller.
.
Signal value:
Pump B relay status
The module has this output socket if the Yes option is selected for the
Outputs the status of the second pump from the cooling distribution circuit controller.
Signal value:
Pump B fault
The module has this output socket if the Yes option is selected for the
for the
Outputs the fault status provided by the second pump.
Signal value:
Pump B repair switch status
The module has this output socket if the Yes option is selected for the
for the
Outputs the contact position provided by the second pump repair switch.
Signal value:
Pump display operating status
parameter.
0 = Inactive
1 = Active
0 = Off
1 = On
Pump display pump fault status
0 = No alarm
1 = Alarm
Display pump repair switch status
0 = Inactive
1 = Active
Double pump
Double pump
Double pump
parameter.
Double pump
parameter.
Data type
DPT 1.011
parameter and the Yes option is selected
DPT 1.001
parameter.
DPT 1.005
parameter and the Yes option is selected
DPT 1.011
parameter and the Yes option is selected
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 353