ABB i-bus
KNX
Parameters
Object function
Input: Heat generator operating status
The module has this group object if the Yes option is selected for the
Input for the operating status (Off/On) provided by the heat generator. Due to the control integrated into the heat generator,
this status may differ from the operating status specified by this module.
Telegram value:
Input: Heat generator failure status
The module has this group object if the Yes option is selected for the
Input for the fault status provided by the heat generator.
Signal value:
In-/Output: Pump override disable/enable Heat generator
The module has this group object if the Yes option is selected for the
This object activates/deactivates the override of the heat generator's pump.
Telegram value:
In-/Output: Pump override value
The module has this group object if the Yes option is selected for the
This object specifies the state with which the heat generator's pump is overridden if the pump override is active.
Telegram value:
320 2CDC508198D0211 Rev. A | AC/S 1.x.1
Name (can be changed separately)
Heat generator
0 = Inactive
1 = Active
Heat generator
0 = Inactive
1 = Active
0 = Disabled
1 = Enabled
Heat generator
0 = Off
1 = On
Data type
1 bit
DPT 1.011
Show operating status
parameter.
1 bit
DPT 1.011
Show fault status
parameter.
1 bit
DPT 1.003
Override by WebUI
parameter.
1 bit
DPT 1.001
Override by WebUI
parameter.
Flags
C, W, T
C, W, T
C, R, W, T
C, R, W, T