ABB i-bus
EIB / KNX
®
4.3
Communication object
4.3.1
Communication objects
AA/S 4.1, Output 1 – 4
Commissioning
Fig. 10: Communication objects Analogue Actuator AA/S 4.1
No.
Function
0-3
Analogue output
1-byte or 2-byte objects with which the value of the output can be set. In 1-byte mode a new
input value can be assumed rapidly or it is possible to dim to the value. The input object can
be time monitored.
(see also object "Alarm Output ...")
4-7
Analogue output
1-byte object or 2-byte object for displaying the current output value.
Object name
Data type
Input value output 1...4
1 Byte EIS 6
DPT 5.001
2 Byte EIS 5
DPT 9.0xx
Status
1 Byte EIS 6
Output 1...4
DPT 5.001
2 Byte EIS 5
DPT 9.0xx
Flags
C, W
C, R, T
15