ABB i-bus
KNX
Parameters
Object function
Input: Fan coil unit, level sensor
The module has this group object if any option except None is selected for the
selected for the Fan coil unit, level sensor parameter.
Input for the signal value from the level sensor in the fan coil unit.
Telegram value:
Input: Radiator, valve
Input for the position (control value) of the radiator valve.
The data point type for the group object is dependent on the settings in the module:
•
If the On/Off option is selected for the
DPT 1.001
Telegram value 0 = Off, 1 = On
•
If the 0...100 % option is selected for the
DPT 5.001
Telegram value 0...100 %
Input: Floor heating, valve
Input for the position (control value) of the floor heating valve.
The data point type for the group object is dependent on the settings in the module:
•
If the On/Off option is selected for the
DPT 1.001
Telegram value 0 = Off, 1 = On
•
If the 0...100 % option is selected for the
DPT 5.001
Telegram value 0...100 %
Name (can be changed
separately)
Room
0 = Off
1 = On
Room
Radiator
parameter:
Radiator
parameter:
Room
Floor heating
Floor heating
Fan coil unit
parameter:
parameter:
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 215
Data type
Flags
1 bit
C, W, T, U
DPT 1.001
parameter and the Yes option is
1 bit DPT 1.001
C, W, T, U
1 byte DPT 5.001
1 bit DPT 1.001
C, W, T, U
1 byte DPT 5.001