ABB i-bus
KNX
Parameters
Input sockets
Object name
Heat generator operating status
This module has this input socket if the Yes option is selected for the
option is selected for the
The heat generator connected can be switched on and off by another module via this input. This is a multiple input socket on
which the input signals are linked via an OR operator.
Signal value:
Supply setpoint temperature External specification
This module has this input socket if the Yes option is selected for the
input socket option is selected for the
Specification of the supply setpoint temperature by another module. This value is output in the corresponding group objects to
the heat generator linked.
The value can be affected by the Max. supply temperature and Supply setpoint temperature offset parameters in the
module.
Signal value:
Outside temperature
This module has this input socket if the Yes option is selected for the
Calculated weather compensated option is selected for the
Input for the outside temperature. The supply setpoint temperature is calculated by the module from the heating curve based
on this value.
Signal value:
312 2CDC508198D0211 Rev. A | AC/S 1.x.1
Enable heat generator based on ASM input socket
0 = Off
1 = On
Supply setpoint temperature source
Note
-273...670760 °C
-273...670760 °C
Data type
DPT 1.001
Supply temperature control
parameter.
DPT 9.001
Supply temperature control
parameter.
DPT 9.001
Supply temperature control
Supply setpoint temperature source
parameter and the Yes
parameter and the ASM
parameter and the
parameter.