Parameters
Object name
Heating distribution circuit: Max. room setpoint temperature
This module has this BACnet output object if the Yes option is selected for the
Calculated weather compensated option is selected for the
the current room setpoint temperatures option is selected for the
Outputs the highest room setpoint temperature that is present on the ASM input socket and that is used by the Economy mode
function.
Signal value:
Heating distribution circuit: Control On/Off
The module has this BACnet output object in the following conditions:
If the Yes option is selected for the
heating distribution circuit control based on ASM input socket
If the Yes option is selected for the
Outputs the status (Off/On) of the control that is sent to the heating distribution circuit controller via the related group object.
The state is dependent on the Enable heating distribution circuit control based on ASM input socket and Switch off if no room
demand functions as well as any override via the web user interface.
Signal value:
Heating distribution circuit: Room involvement
The module has this BACnet output object if the Yes option is selected for the
Calculated weather compensated option is selected for the
is selected for the
Outputs of current value by which the supply setpoint temperature is increased or reduced by the Room involvement function.
Signal value:
280 2CDC508198D0211 Rev. A | AC/S 1.x.1
-273...670760 °C
Supply temperature control
Switch off if no room demand
0 = Off
1 = On
Room involvement
parameter.
-273...670760 °C
Object type
Analog value
Supply temperature control
Supply setpoint temperature source
Economy mode
parameter.
Binary value
parameter and the Yes option is selected for the
parameter.
parameter.
Analog value
Supply temperature control
Supply setpoint temperature source
Unit
COV send
condition
°C (62)
1.0
parameter, the
parameter and the Based on
-
-
Enable
°C (62)
1.0
parameter, the
parameter and the Yes option