ABB i-bus KNX AC/S 1.x.1 Series Product Manual page 186

Application controller
Table of Contents

Advertisement

®
ABB i-bus
KNX
Parameters
Selection of all options except Display:
186 2CDC508198D0211 Rev. A | AC/S 1.x.1
Dependent parameter(s):
Room setpoint temperature type
Options:
Absolute setpoint temperatures
Relative setpoint temperatures
This parameter specifies whether the room thermostat uses absolute or relative room setpoint
temperatures. This setting does not affect the indication on the web user interface.
Absolute setpoint temperatures: The room thermostat uses absolute room setpoint
temperatures e.g. 23 °C.
For the new master/slave interface a group object of type DPT 9.001 is used.
For the old master/slave interface a group object of type DPT 6.010 is used.
Relative setpoint temperatures: The room thermostat uses relative room setpoint temperatures
e.g. +3 K.
For the new master/slave interface a group object of type DPT 9.002 is used.
For the old master/slave interface a group object of type DPT 6.010 is used.