User-Programmable Inverse-Time Characteristics - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
11.2.1.2
11.2.1.3
615 series ANSI
Technical Manual

User-programmable inverse-time characteristics

The user can define curves by entering parameters into the following standard formula:
A
t s
B k
[ ]
=
+
c
I
E
 −
I
>
A060641 V3 EN
t[s] Trip time (in seconds)
A
set
Curve parameter A
Curve parameter B
B
set
Curve parameter C
C
set
Curve parameter E
E
set
I
Measured current
Pickup value
I>
set
Time multiplier
k
set
RI and RD-type inverse-time characteristics
The RI-type simulates the behavior of electromechanical relays. The RD-type is a ground-
fault specific characteristic.
The RI-type is calculated using the formula
k
t s
[ ]
=
I
>
 
0 339 0 236
.
.
×
I
A060642 V2 EN
The RD-type is calculated using the formula
I
t s
[ ]
5 8 1 35 In
.
.
=
×
k I
× >
A060643 V2 EN
General function block features
 
Section 11
(Equation 174)
(Equation 175)
(Equation 176)
1097