Section 10
Power quality measurement functions
10.4.7
Table 940:
PQVUB Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Unb detection method
1=Neg Seq
2=Zero Seq
3=Neg to Pos Seq
4=Zero to Pos Seq
5=Ph vectors Comp
Unbalance pickup Val
1...100
Trigger mode
1=Single
2=Periodic
3=Continuous
Percentile unbalance
1...100
Obs period selection
1=1 Hour
2=12 Hours
3=1 Day
4=7 Days
5=User defined
User Def Obs period
1...168
Obs period Str year
2008...2076
Obs period Str month
0=reserved
1=January
2=February
3=March
4=April
5=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
Obs period Str day
1...31
Obs period Str hour
0...23
1070

Settings

Unit
Step
%
1
%
1
h
1
h
Default
Description
1=enable
Opeartion Enable/Disable
3=Neg to Pos Seq
Set the operation mode for voltage unbalance
calculation
1
Voltage unbalance pickup value
3=Continuous
Specifies the observation period triggering
mode
95
The percent to which percentile value
PCT_UNB_VAL is calculated
5=User defined
Observation period for unbalance calculation
168
User define observation period for statistic
calculation
2011
Calendar time for observation period start year
in YYYY
1=January
Calendar time for observation period start
month
1
Calendar time for observation period start day
0
Calendar time for observation period start hour
1MAC059074-MB A
615 series ANSI
Technical Manual