For Customers Replacing The Conventional Model With This Inverter; Replacement Of The Fr-A740 Series - Mitsubishi Electric FR-A802-E Instruction Manual

Separated converter type
Table of Contents

Advertisement

7
APPENDIX
APPENDIX provides the reference information for use of this product.
Refer to APPENDIX as required.
7.1
For customers replacing the conventional model
with this inverter
7.1.1

Replacement of the FR-A740 series

 Differences and compatibility with the FR-A740 series
Item
Control method
Added functions
V/F control
Advanced
magnetic flux
vector control
Real sensorless
vector control
Vector control
PM sensorless
vector control
PID control
Automatic restart after
instantaneous power
failure
Number of motor poles
V/F control switching
PTC thermistor input
USB connector
Control circuit terminal
block
Terminal response level
PU
Plug-in option
Communication option
Installation size
Converter
DC reactor
Brake unit
124
7. APPENDIX

7.1 For customers replacing the conventional model with this inverter

FR-A740
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control (with plug-in option)
PM sensorless vector control (IPM motor)
400 Hz
120 Hz
120 Hz
120 Hz
300 Hz
Turn the X14 signal ON to enable PID control.
Turn the CS signal ON to enable restart.
The V/F switchover (X18) signal is valid when Pr.81 =
"12 to 20" (2 to 10 poles).
Input through terminal AU (The function of terminal AU
is switched by a switch.)
B connector
Removable terminal block (screw type)
The FR-A800's I/O terminals have better response level than the FR-A700's terminals. By setting Pr.289 Inverter
output terminal filter and Pr.699 Input terminal filter, the terminal response level can be compatible with that of
FR-A700. Set to approximately 5 to 8 ms and adjust the setting according to the system.
FR-DU07 (4-digit LED)
FR-PU07
Dedicated plug-in options (not interchangeable)
Connected to the connector 3
Installation size is not compatible. (New mounting holes are required.)
Built-in for all capacities
DC reactor (FR-HEL) is provided.
FR-BU2, MT-BU5
FR-A842
V/F control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control (with plug-in option)
PM sensorless vector control (IPM/SPM motor)
USB host function
Safety stop function
etc.
590 Hz
400 Hz
400 Hz
400 Hz
400 Hz
When the X14 signal is not assigned, just set a value in
Pr.128 to enable PID control.
When the X14 signal is assigned, turn the X14 signal ON
while Pr.128 ≠ "0" to enable PID control.
The PID pre-charge function and dancer control are
added.
The CS signal does not need to be assigned. (Restart is
enabled with the Pr.57 setting only.)
Pr.81 = "12" (12 poles)
The X18 signal is valid regardless of the Pr.81 setting.
(The Pr.81 settings "14 to 20" are not available.)
Input through terminal 2 (The function of terminal 2 is
switched by the Pr.561 setting.)
Mini B connector
Removable terminal block (spring clamp type)
FR-DU08 (5-digit LED)
FR-PU07 (Some functions are unavailable.)
The FR-DU07 is not supported.
Connected to the connector 1
The converter unit (FR-CC2) is required.
Built in the converter unit (FR-CC2)
FR-BU2