Appendix1 For Customers Replacing The Conventional Model With This Inverter - Mitsubishi Electric FR-CC2-H355K Instruction Manual

F800 series, fr-f802 separated converter type
Hide thumbs Also See for FR-CC2-H355K:
Table of Contents

Advertisement

Appendix1
Appendix1.1
Difference and compatibility with FR-F740(P) series
Item
Control method
Added functions
V/F control
Advanced
magnetic flux
vector control
PM motor control
PID control
Automatic restart after
instantaneous power
failure
PTC thermistor input
USB connector
Control circuit terminal block
Terminal response level
PU
Plug-in option
Plug-in option connector
Communication option
Installation size
Converter
DC reactor
Brake unit
Installation precautions
• Removal procedure of the front cover is different. (Refer to
• Plug-in options of the FR-F700(P) series are not compatible.
• Operation panel (FR-DU07) cannot be used.
102
APPENDIX
For customers replacing the
conventional model with this
inverter
Replacement of the FR-F740(P) series
FR-F740(P)
V/F control
Simple magnetic flux vector control
IPM motor control
-
400 Hz
-
-
Turn the X14 signal ON to enable PID control.
Turn the CS signal ON to enable restart.
Pr.186 CS terminal function selection initial
value "6"
Input from the terminal AU
(The function of the terminal AU is switched by
a switch.)
-
Removable terminal block (screw type)
The FR-F800's I/O terminals have better response level than the FR-F700(P)'s terminals. By setting
Pr.289 Inverter output terminal filter and Pr.699 Input terminal filter, the terminal response level can be
compatible with that of FR-F700(P). Set to approximately 5 to 8 ms and adjust the setting according to the
system.
FR-DU07 (4-digit LED)
FR-PU07
Dedicated plug-in options (not interchangeable)
One connector (FR-F700P, FR-F700-CHT)
Two connectors (FR-F700-NA/EC)
Connected to the connector 1. (FR-F700P, FR-
F700-CHT)
Connected to the connector 2. (FR-F700-NA/EC)
Installation size is not compatible. (New mounting holes are required.)
Built in for all capacities
DC reactor (FR-HEL) is provided.
FR-BU2, MT-BU5
V/F control
Advanced magnetic flux vector control
PM motor control (IPM motor/SPM motor)
USB host function
Safety stop function
etc.
590 Hz
400 Hz
400 Hz
When the X14 signal is not assigned, just set a value
other than "0" in Pr.128 to enable PID control.
When the X14 signal is assigned, turn the X14 signal ON
while Pr.128 ≠ "0" to enable PID control.
CS signal assignment not required. (Restart is enabled
with the Pr.57 setting only.)
Pr.186 CS terminal function selection initial value
"9999"
Input from the terminal 2.
(The function of the terminal 2 is switched by the Pr.561
setting.)
Mini B connector
Removable terminal block (spring clamp type)
FR-DU08 (5-digit LED)
FR-PU07 (Some functions, such as parameter copy, are
unavailable.)
FR-DU07 is not supported.
Three connectors
Connected to the connector 1.
The converter unit (FR-CC2) is required.
Built in the converter unit (FR-CC2)
FR-BU2