12.2
Monitor item selection on operation panel or via
communication
The monitor item to be displayed on the operation panel can be selected.
Pr.
52
Operation panel main
M100
monitor selection
774
Operation panel monitor
M101
selection 1
775
Operation panel monitor
M102
selection 2
776
Operation panel monitor
M103
selection 3
992
Operation panel setting dial
M104
push monitor selection
170
Watt-hour meter clear
M020
563
Energization time carrying-
M021
over times
268
Monitor decimal digits
M022
selection
891
Cumulative power monitor
M023
digit shifted times
171
Operation hour meter clear
M030
564
Operating time carrying-
M031
over times
290
Monitor negative output
M044
selection
1106
Torque monitor filter
M050
1107
Running speed monitor
M051
filter
1108
Excitation current monitor
M052
filter
*1
The setting range differs depending on the model. For more information, refer to Monitor item list.
270
12. (M) Item and Output Signal for Monitoring

12.2 Monitor item selection on operation panel or via communication

Name
Initial value
0 (output
frequency)
9999
0 (set frequency)
9999
0
9999
9999
9999
0
0
9999
9999
9999
Setting range
0, 5 to 14, 17 to
20, 23 to 25, 32,
33, 35, 38, 40 to
Select the monitor item to be displayed on the operation
42, 44, 45, 50 to
panel.
57, 61, 62, 67,
Refer to
page 271
83, 91, 97,
*1
100
1 to 3, 5 to 14,
17 to 20, 23 to
Each of the initial monitor items displayed on the operation
25, 32, 33, 35,
panel in the monitor mode (output frequency, output current,
38, 40 to 42, 44,
and output voltage) can be switched to a user-designated
45, 50 to 57, 61,
item.
62, 67, 83, 91,
9999: Follows the Pr.52 setting.
*1
97, 100, 9999
0 to 3, 5 to 14,
17 to 20, 23 to
25, 32, 33, 35,
Select the monitor item displayed on the operation panel at
38, 40 to 42, 44,
the time when the setting dial is pressed. (Available for the
45, 50 to 57, 61,
standard model only.)
62, 67, 91, 97,
100
0
Set "0" to clear the watt-hour meter.
Set "10" to monitor the cumulative power in the range of 0 to
10
9999 kWh via communication.
Set "9999" to monitor the cumulative power in the range of
9999
0 to 65535 kWh via communication.
(0 to 65535)
The number of times that the cumulative energization time
(Read-only)
exceeded 65535 hours is displayed (read-only).
0
Value is displayed in 1 increments (an integer).
1
Value is displayed in 0.1 increments.
9999
No function
Set the number of digits to move the decimal point of the
0 to 4
cumulative energy monitored value to the left. The readout
peaks out at the upper limit of readout.
The function of moving the decimal point is not available.
9999
The readout is reset to 0 when it exceeds the upper limit.
0
Set "0" to clear the operation hour meter.
The readout is always 9999. Nothing changes when "9999"
9999
is set.
(0 to 65535)
The number of times that the operating time reaches 65535
(Read-only)
hours is displayed. Read-only.
Set the availability of negative signal output via terminal AM,
0, 1, 4, 5, 8, 9,
through communication, and to the FR-A8AY. (Refer to
12, 13
page
278.)
The filter time constant is selectable for monitoring of the
0 to 5 s
torque. A larger setting results in slower response.
9999
0.3 s filter
The filter time constant is selectable for monitoring of the
0 to 5 s
running speed. A larger setting results in slower response.
9999
0.08 s filter
The filter time constant is selectable for monitoring of the
0 to 5 s
motor excitation current. A larger setting results in slower
response.
9999
0.3 s filter
Description
for the monitor item selection.