Major Alarm Inquiry Test (#142) - Avaya S8700 Maintenance Manual

Avaya s8700 media server for ip connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Maintenance Object Repair Procedure
Table 8-529. Test #141 Yellow Alarm Inquiry Test — Continued
Error
Test
Code
Result
Description / Recommendation
PASS
Neither a Yellow alarm nor a Remote Multiframe Alarm nor a F5 state alarm is
being received from the remote DS1 endpoint.
0
NO
The test could not relate the internal ID to the port (no board). This could be
BOARD
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Verify that the board's translations are correct. Execute the add ds1
2. If the board was already administered correctly, check the error log to
3. If the board was found to be correctly inserted in step 1, then issue the
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the linkage between the internal ID and the port.

Major Alarm Inquiry Test (#142)

The Major alarm raised by a UDS1 Interface circuit pack indicates that the
average bit error rate on the DS1 facility is greater than 1/1000. The Major Alarm
Inquiry test is used to determine that the received DS1 bit error rate is greater
than 1/1000. The UDS1 Interface circuit pack takes 10 seconds to recognize and
report a Major alarm and 10 seconds to recognize and report that a Major alarm
condition is cleared.
When the UDS1 Interface circuit pack detects a Major alarm, it sends a
MAJOR-ALARM message to the maintenance software. (32-channel interfaces
send a YELLOW alarm to the far end). After the maintenance software receives a
MAJOR-ALARM message, the Major Alarm Inquiry test is initiated to confirm the
Major alarm on the UDS1 Interface circuit pack. The Inquiry test runs every 10
minutes until the Major alarm is cleared. The maintenance software places every
trunk or port on the circuit pack in the out-of-service state if the Major alarm
persists for more than 20 minutes.
When the Major alarm is cleared, the maintenance software restores every trunk
or port on the circuit pack to its previous service state before a Major alarm
occurs.
8-1264
Issue 1 May 2002
UUCSS command to administer the UDS1 interface if it is not already
administered.
determine whether the board is hyperactive. If so, the board is shut down.
Reseating the board will re-initialize it.
busyout board command.
Continued on next page
555-233-142