Maintenance Object Repair Procedure
Table 8-526. Test #138 Loss of Signal Alarm Inquiry Test — Continued
Error
Test
Code
Result
Description / Recommendation
FAIL
UDS1 Interface circuit pack detects a Loss of Signal alarm. The physical link is
broken or the remote DS1 endpoint is down. Every trunk or port of this UDS1
interface circuit pack is out-of-service. If the UDS1 Interface circuit pack is
designated as the supplier of the system synchronization source, then the
system synchronization maintenance will adopt a source elsewhere. See
''SYNC (Port-Network Synchronization)'' on page 8-1034
UDS1 connects to a T1 network facility:
1. Check the physical connection of the UDS1 Interface circuit pack and the
2. If the UDS1 Interface circuit pack connects to a T1 facility, call the vendor
If the UDS1 connects to a line-side terminating device such as a PRI terminal
adapter:
1. Check the physical connection of the UDS1 Interface circuit pack to the
2. Contact the vendor of the line-side terminating device to diagnose the
1300
FAIL
The CSU module is missing.
The CSU module is missing: The
ds1 form has been administered as
is not physically connected to the UDS1 board behind the port carrier.
1. If using the 120A1 CSU module, plug the CSU module into the UDS1
2. Run the test again.
8-1246
Issue 1 May 2002
cable. If a CSU module is physically connected to a UDS1-BD board
behind the port carrier, check the physical connection of the CSU module
and make sure the Network Interface cable is plugged into the CSU
module's NETWORK jack.
of the T1 carrier to diagnose the remote DS1 endpoint. If the UDS1
Interface circuit pack connects directly to a switch, call the system
technician of the remote switch to diagnose the DS1 endpoint.
terminating device. Check premise distribution system (or intra-premise
wiring) for physical connection failures. If a CSU module is physically
connected to a UDS1-BD board behind the port carrier, check the physical
connection of the CSU module and make sure the Network Interface cable
is plugged into the CSU module's NETWORK jack.
equipment.
circuit pack's connector on the I/O connector panel on back of the carrier.
Otherwise, change the
Near-End CSU Type
ds1 form to
.
other
for details. If the
Near-End CSU Type
but the 120A1 CSU module
integrated
field using the change
Continued on next page
field on the add
555-233-142