Counter Module, Pulse Output Module - Omron CS1W-MCH71 Operation Manual

Sysmac cs/cj-series
Hide thumbs Also See for CS1W-MCH71:
Table of Contents

Advertisement

Connecting MECHATROLINK Devices
3-5-4

Counter Module, Pulse Output Module

Communications setting
For counter modules and pulse output modules, MECHATROLINK communi-
cations can be set using the DIP switches.
SW (Default setting)
1
2
3
4
5
ON
OFF
Transmission setting
MECHATROLINK communications can be specified using the DIP switches
(SW) 6 to 8.
See the table below.
Any change of the settings becomes valid after turning OFF the power once,
then ON again.
Pin
Name
6
Baud rate
7
Transmission bytes OFF
8
Station address
Station address setting
Station address can be set as shown in the table below using the DIP switch 1
to 5 (SW).
The bit 5 of SW specifies the number of 10s while the bit 1 to 4 of SW speci-
fies the number of units.
Do not change the setting while the power is being supplied.
5
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
to
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
to
ON
ON
ON
6
7
8
Setting
Content
OFF
4 Mbps
ON
10 Mbps
17 byte
ON
30 byte
OFF
Refer to Station
address setting
ON
SW
3
2
1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
ON
ON
Section 3-5
Default setting
OFF
OFF
ON (Do not set to OFF.)
Station address
Do not set.
1 (01H): Default setting
2 (02H)
3 (03H)
to
15 (0FH)
16 (10H)
17 (11H)
18 (12H)
19 (13H)
to
Do not set.
51