System Variables - Omron CS1W-MCH71 Operation Manual

Sysmac cs/cj-series
Hide thumbs Also See for CS1W-MCH71:
Table of Contents

Advertisement

System Variables

4-5
System Variables
4-5-1
System Variables
Variable
IORD
Group
Address
Address
SW0000
3000
Unit
SW0001
Unit
SW0002
3001
Unit
SW0003
SW0004
3002
Unit
SW0005
SW0006
3003
SW0007
SW0008
3004
SW0009
SW000A
3005
SW000B
SW000C
3006
Unit
SW000D
SW000E
3007
Unit
SW000F
SW0010
3008
Unit
SW0011
System variables are all in read-only area; they cannot be written.
When reading with the IORD instruction, the size is always two words (4
bytes).
Name
Unit Cycle Time
Outputs unit cycle time (SH4).
MECHATROLINK-II
Outputs the MECHATROLINK-II Com-
Communication Cycle
munication Cycle.
Operation Mode
Outputs the MC Unit operation mode
0: RUN mode
1: CPU mode
2: Tool mode
Product ID
Bit 00
(Supported in Unit Ver.
0: CS1W-MCH71 Unit Ver. 2.0 or earlier
3.0 or later)
1: Other unit versions
Forced Stop Request
Indicates forced stop request from the
from the Tool: Detail of
tool.
the request
Bit00: Axis: task stop
Bit01: Axis, task stop cancel
Bit06: Cam Data buffer copy
Bit07: Program buffer copy
Forced Stop Request
Indicates forced stop request from the
from the Tool: Object 1
tool.
Bit00-07: 0/1 Motion task
1-8With/without forced stop request
Bit08: 0/1 Reserved
Forced Stop Request
Indicates forced stop request from the
from the Tool: Object 2
tool.
Bit00-31: 0/1 Axis
1-32With/without forced stop request
Reserved
Reserved
Status of Forced Stop
Indicates status of forced stop from the
from the Tool: Object 1
tool.
Bit00-07: 0/1 Motion task
1-8in progress/being stopped
Bit08: 0/1 Reserved
Status of Forced Stop
Indicates status of forced stop from the
from the Tool: Object 2
tool.
Bit00-31: 0/1 Axis
1-32in progress/being stopped
No. of Unit Scan Execu-
Indicates the No. of unit scan execu-
tions
tions.
No. of Self-diagnosis
Indicates the No. of self-diagnosis exe-
executions
cutions in background.
Error log: No. of stored
Outputs No. of error logs after the power
records
has been turned ON. 0-20
Error log: No. of actual
Outputs No. of error logs after the power
records
has been turned ON. (For system man-
agement) 0-64000
The most recent error is stored in the
error log whose number is the remain-
der of the value output here divided by
20.
Description
0.5 ms
0.5 ms
Nil
Nil
Nil
Nil
Nil
Reserved
Nil
Nil
Times
Times
Record
Record
Section 4-5
Unit
Update timing
When power is
turned ON
When power is
turned ON
When operation
mode is changed
When power is
turned ON
FINS: Task Con-
trol setting
FINS: Task Con-
trol Setting
FINS: Task Con-
trol Setting
Reserved
Unit Scan
Unit Scan
Unit Scan
When executing
Self-diagnosis
Error occurrence
Error occurrence
111

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Cj1w-mch71

Table of Contents