System Parameters
Number
Address
P00004
5003h
P00005
5004h
P00006
5005h
P00007
5006h
P00008
5007h
P00009
5008h
P00010
5009h
P00011
500Ah
P00012
500Bh
P00013
500Ch
-
-
P00032
501Fh
Motion Task Parameters
Note
No.
Address
M = 1-8
M = 0-7
P00M01
5020h +
(M * 20h)
P00M02
5021h +
(M * 20h)
P00M03
5022h +
(M * 20h)
P00M04
5023h +
(M * 20h)
P00M05
5024h +
(M * 20h)
60
Name
Unit function select
• Specifies method of specifying the speed in helical cir-
cular interpolation under MOVEC command.
• Specifies center-positioning method for MOVEC com-
mand
• Specifies the speed command unit for SPEED com-
mand/feedback speed.
• Selects output method for positioning completed/posi-
tioning completed 2 signals.
• Specifies the method for changing the direction for JOG
operation.
• Specifies support for 3-ms communications cycle.
• Specifies the type of continuous operation for multi-turn
operation for an infinite axis
• Specifies behavior when an overtravel alarm occurs
• Specifies the number of parallel branches for each Unit
and each task.
• Specifies origin establishment and status hold for
present position preset.
• Specifies the operation (deceleration stop or servo OFF)
for deceleration stop signal inputs.
Reserved
General I/O Dis-
Specifies general I/O signals disable/enable for MC unit.
abled/Enabled
Input control 1 from
Specifies whether input signals from CPU to the Unit or
PLC
motion tasks are enabled or disabled.
Input control 2 from
Specifies whether input signals from CPU to axes are
PLC
enabled or disabled.
Setting for the No. of
• No. of retrial nodes: Specifies the number of nodes to be
MECHATROLINK-II
retried within MECHATROLINK-II communication cycle.
Retrial Nodes, With/
• With/without C2 master: Set this parameter when there
without C2 master
is a master unit other than MC unit. (reserved)
MECHATROLINK-II
Specifies the time to make the communication start
Delay in Communi-
delayed in order to wait for slave startup.
cation Start
Number of zone bits
Specifies the number of zone bits to be used.
Zone data leading
Specifies the leading address for the zone data (upper
address
and lower limits) used by the zone bits.
Reserved
Abbreviation in the No. column:
Abbreviation in the address column: M = 0 to 7 (motion task number − 1)
Name
Max. interpolation
Sets the maximum feed rate (F command) in interpolation
feed rate
operation
Interpolation feed
Sets the time required to accelerate from zero to max.
acceleration time
interpolation feed rate.
Interpolation feed
Sets the time required to decelerate from max. interpola-
deceleration time
tion feed rate to zero in interpolation.
Interpolation S-curve
Selects enable /disable of S-curve filter at the interpola-
filter enabled
tion feed rate.
Interpolation S-curve
Sets the S-curve filter time constant at the interpolation
time constant
feed rate.
Function
M = 1 to 8 (motion task number)
Function
Section 4-2
Page
68
70
71
72
74
74
page 75
page 75
---
Page
76
76
77
77
78

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Cj1w-mch71

Table of Contents