Chapter 13 Warning CodesCFP2000
ID No.
Display on LCD Keypad
10
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Check if the ambient temperature
or temperature inside the cabinet
is too high, or if there is obstruction
in the ventilation hole of the control
cabinet.
Check if there is any obstruction on
the heat sink or if the fan is running
Insufficient ventilation space
Check if the drive matches the
corresponded loading
The drive has run 100% or more of
the rated output for a long time
Unstable power
The load changes frequently
oH1/ oH2 warning level
Model
VFD007FP4EA-41/52/52S
VFD015FP4EA-41/52/52S
VFD022FP4EA-41/52/52S
VFD037FP4EA-41/52/52S
VFD040FP4EA-41/52/52S
VFD055FP4EA-41/52/52S
VFD075FP4EA-41/52/52S
VFD110FP4EA-41/52/52S
VFD150FP4EA-41/52/52S
VFD185FP4EA-41/52/52S
VFD220FP4EA-41/52/52S
VFD300FP4EA-41/52/52S
VFD370FP4EA-41/52/52S
VFD450FP4EA-41/52/52S
VFD550FP4EA-41/52/52S
VFD750FP4EA-41/52/52S
VFD900FP4EA-41/52/52S
Warning Name
Capacitor over-heat
The drive has detected over heat of the capacitor
warning (oH2)
Action and Reset
oH2 error level minus (–) 5°C
The oH2 warning occurs when the capacitor temperature is higher than oH2
warning level
N/A
Auto-reset
The drive auto-resets when the capacitor temperature is lower than oH2 error
level minus (–) 10°C
N/A
1. Check the ambient temperature.
2. Regularly inspect the ventilation hole of the control cabinet.
3. Change the installed place if there are heating objects, such as braking
resistors, in the surroundings.
4. Install/ add cooling fan or air conditioner to lower the temperature inside the
cabinet.
Remove the obstruction or replace the cooling fan.
Increase ventilation space of the drive.
1. Decrease loading.
2. Decrease the carrier.
3. Replace with a drive with larger capacity.
Replace with a drive with larger capacity.
Install reactor(s).
Reduce the changes of the load.
oH1
oH2
110
85
100
105
90
110
97
100
90
95
85
13-8
Description
Corrective Actions
oH warning
oH1 warning = (Pr. 06-15)
oH1 Warning = Pr.06-15
oH2 Warning = oH2 – 5
Unit: °C