Delta CFP2000 Series User Manual page 446

Ip55 fan and pump drive
Table of Contents

Advertisement

 Basic Motor Parameters Adjustment
1. Parameter reset:
Reset Pr.00-02=10 (60 Hz) to the default value.
2. Select PM motor type:
Pr.05-33=1 (SPM) or 2 (IPM)
3. Motor nameplate parameter setting:
Parameter
Pr.01-01
Pr.01-02
Pr.05-34
Pr.05-35
Pr.05-36
Pr.05-37
4. PM parameter auto-tuning:
5. Set Pr.05-00=5 (Rolling auto-tuning for PM) or 13 (Static auto-tuning for PM) and press "RUN"
key to finish motor auto-tuning, then you will get the following parameters:
Parameter
Pr.05-39
Pr.05-40
Pr.05-41
Pr.05-43
If an auto-tuning error (AUE) occurs, refer to Section 14 "Fault Codes and Descriptions" for
further treatment.
AUE Error (code)
AUE (40)
AUE1 (142)
AUE2 (143)
6. Set control mode
Control mode for the drive: Pr.00-10 = 0: Speed mode
Control mode for the motor: Pr.00-11 = 2: PM SVC mode
7. Measure the initial magnetic pole angle of PM
Set Pr.10-53 PM initial rotor position detection method
0: Disable
1: Force attracting the rotor to zero degrees
2: High frequency injection
3: Pulse injection
(Set to 2 for IPM; set to 3 for SPM. If these settings cause problems, then set the parameter to
1.)
Description
Rated frequency (Hz)
Rated voltage (V
)
AC
Rated current (A)
Rated power (kW)
Rated rotor speed (rpm)
Number of poles for the motor (poles)
Stator resistance for a permanent magnet motor (Ω)
Permanent magnet motor Ld (mH)
Permanent magnet motor Lq (mH)
Ke parameter of a permanent magnet motor (V
(When Pr.05-00=5, the Ke parameter is measured based on the actual
motor rotation.)
(When Pr.05-00=13, the Ke parameter is automatically calculated
based on the motor power, current and rotor speed.)
Auto-tuning error
Auto-tuning error 1 (No feedback current error)
Auto-tuning error 2 (Motor phase loss error)
12.2-00-3
Chapter 12 Description of Parameter SettingsCFP2000
Description
phase , rms
Description
/ krpm)