Delta CFP2000 Series User Manual page 290

Ip55 fan and pump drive
Table of Contents

Advertisement

Settings
Functions
Error output selection 3
37
(Pr.06-25)
Error output selection 4
38
(Pr.06-26)
Speed reached
40
(including STOP)
44
Low current output
UVW output
45
electromagnetic valve
switch
46
Master dEb output
Output control for
50
CANopen
Chapter 12 Description of Parameter SettingsCFP2000
Active when Pr.06-25 is ON.
Active when Pr.06-26 is ON.
Active when the output frequency reaches the setting frequency or
stopped.
This function needs to be used with Pr.06-71–Pr.06-73
Use this function with external terminal input = 49 (drive enabled) and
external terminal output = 45 (electromagnetic valve enabled), and
then the electromagnetic valve is ON or OFF according to the status of
the drive.
When dEb rises at master, MO sends a dEb signal to the slave.
Output the message when the master triggers dEb. This ensures that
the slave also triggers dEb. Then slave follows the deceleration time
of the master to stop simultaneously with the master.
Control multi-function output terminals through CANopen.
To control RY2, set Pr.02-14 = 50.
The mapping table of the CANopen DO is shown in the following table:
Physical
Setting of related
terminal
parameters
RY1
Pr.02-13 = 50
RY2
Pr.02-14 = 50
RY3
Pr.02-15 = 50
MO10/RY10
Pr.02-36 = 50
MO11/RY11
Pr.02-37 = 50
RY12
Pr.02-38 = 50
RY13
Pr.02-39 = 50
RY14
Pr.02-40 = 50
RY15
Pr.02-41 = 50
Refer to Section 15-3-5 for more information.
12.1-02-13
Descriptions
Attribute
Corresponding Index
RW
The bit0 at 2026-41
RW
The bit1 at 2026-41
RW
The bit2 at 2026-41
RW
The bit5 at 2026-41
RW
The bit6 at 2026-41
RW
The bit7 at 2026-41
RW
The bit8 at 2026-41
RW
The bit9 at 2026-41
RW
The bit10 at 2026-41