Delta CFP2000 Series User Manual page 330

Ip55 fan and pump drive
Table of Contents

Advertisement

05 Motor Parameters
The following are abbreviations for different types of motors:
IM: Induction motor
PM: Permanent magnet synchronous AC motor
IPM: Interior permanent magnet synchronous AC motor
SPM: Surface permanent magnet synchronous AC motor
Motor Parameter Auto-Tuning
Settings
 Refer to Section 12-2 "Adjustment and Application" for more details of motor adjustment process.
Full-load Current for Induction Motor 1 (A)
Settings
 Sets this value according to the rated current of the motor as indicated on the motor nameplate.
 The default is 90% of the drive's rated current.
Example: The rated current for a 7.5 HP (5.5 kW) is 25 A. The default is 22.5 A.
The setting range is between 2.5–30 A. (25*10%=2.5 A and 25*120%=30 A)
Rated Power for Induction Motor 1(kW)
Settings
 Sets the rated power for motor 1. The default is the drive's power value.
Rated Speed for Induction Motor 1 (rpm)
Settings
 Sets the rated speed for the motor as indicated on the motor nameplate.
 Pr.01-01 and Pr.05-04 determine the maximum rotor speed for IM.
For example: Pr.01-01=20 Hz, Pr.05-04=2, according to the equation 120 x 20 Hz / 2 = 1200 rpm
and take integers. Due to the slip of the IM, the maximum setting value for Pr.05-03 is 1199 rpm
(1200 rpm – 1).
0: No function
1: Rolling auto-tuning for induction motor (IM)
2: Static auto-tuning for induction motor (IM)
5: Rolling auto-tuning for PM (IPM / SPM)
13: Static auto-tuning for PM (IPM / SPM)
Depending on the model power
0.00
655.35 kW
0–xxxx rpm (Depending on the motor pole number)
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
Chapter 12 Description of Parameter SettingsCFP2000
 This parameter can be set during operation.
12.1-05-1
Default: 0
Default: Depending on
the model power
Default: Depending on
the model power
Default: Depending on
the motor pole number