Master Frequency Command Source (HAND)
Settings
Determines the master frequency source in HAND mode.
Operation Command Source (HAND)
Settings
Determines the operation frequency source in HAND mode.
Use Pr.00-20 and Pr.00-21 to set the frequency source and the operation source in AUTO mode,
and use Pr.00-30 and Pr.00-31 to set the frequency source and operation source in HAND mode.
Select or switch AUTO / HAND mode by using the digital keypad KPC-CC01 or setting the
multi-function input terminal (MI).
The default for the frequency source or operation source is AUTO mode. It returns to AUTO
mode whenever you cycle the power. If you use a multi-function input terminal to switch AUTO /
HAND mode, the multi-function input terminal has the highest priority. When the external terminal
is OFF, the drive does not accept any operation signal and cannot execute JOG.
Digital Keypad STOP Function
Settings
This parameter is valid when the digital keypad is not set as the operation command source
(Pr.00-21≠0). When Pr.00-21=0, the STOP key on the digital keypad is not affected by this
parameter.
Display Filter Time (Current)
Settings: 0.001–65.535 sec.
Minimizes the current fluctuation displayed by digital keypad.
Display Filter Time (Keypad)
Settings: 0.001–65.535 sec.
Minimizes the value fluctuation displayed by digital keypad.
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (does not include CANopen card)
0: Digital keypad
1: External terminals
2: RS-485 serial communication
3: CANopen communication card
5: Communication card (does not include CANopen card)
0: STOP key disable
1: STOP key enable
12.1-00-13
Chapter 12 Description of Parameter SettingsCFP2000
Default: 0
Default: 0
Default: 0
Default: 0.100
Default: 0.100